● DSP digital control technology
● Active power factor correction (APFC), input power factor up to 0.99
● Output power factor 0.9
● Cold start
● Dual input
● Wide input voltage range (190 V ~ 485 V)
● Auto sensing frequency
● 50 / 60 Hz frequency conversion mode
● Work efficiency up to 98% in ECO mode
● Auto control fan speed when loads varies
● Auto power ON/OFF according to the load capacity set by users
● Flexible battery configuration for using 14/16/18/20 pcs batteries
● Compact internal layout, miniaturized the complete unit for small footprint
● LCD+LED display, multi-functional keys operation, friendly human-machine interface
● Powerful background software for parameters configuration and online updating
● Doubling the battery charging speed, 90% capacity restored in 4 hours (standard model UPS)
● Linear derating in low voltage input, reducing battery discharging times, extending the service life of battery
● Advanced battery management (ABM), automatic floating / equalizing charge control, charger dormancy control
● Configurable switching time from battery mode to mains mode when mains power is restored, reducing the impact on
power grid or generator
● Effective software and hardware protection function, powerful self-diagnostic function, abundant historical records
● Standard emergency power off (EPO)
● Standard maintenance bypass
● Standard RS232 / USB communication port
● Optional RS485 / SNMP / AS400 communication port and SMS alarms
● Optional N+X redundancy parallel up to 6 units
● Optional battery temperature compensation, EMD environmental sensors
● Optional 5” LCD touch screen display
MODEL | EA9010P | EA9012P | EA9015P | EA9020P | EA9030P |
Capacity | 10 kVA / 9 kW | 12 kVA / 10.8 kW | 15 kVA / 13.5 kW | 20 kVA / 18 kW | 30 kVA / 27 kW |
INPUT | |||||
Rated voltage | 360 V / 380 V / 400 V / 415 Vac | ||||
Voltage range | 277 ~ 485 Vac (no derating) 190 ~ 277 Vac (linear derating between 50% and 100% load) | ||||
Rated frequency | 50 / 60 Hz (auto-sense) | ||||
Frequency range | 40 ~ 70 Hz | ||||
Power factor | ≥ 0.99 | ||||
Total harmonic distortion (THDI) | ≤ 3% | ||||
Bypass voltage range | -40% ~ +15% (settable) | ||||
OUTPUT | |||||
Voltage | 360 V / 380 V / 400 V / 415 Vac (settable) | ||||
Voltage regulation | ± 1% | ||||
Frequency | 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode) | ||||
Waveform | Sinusoidal | ||||
Crest factor | 3:1 | ||||
Total harmonic distortion (THDV) | ≤ 2% (linear load); ≤ 5% (non-linear load) | ||||
Transfer time | Mains mode to battery mode: 0 ms; Inverter mode to bypass mode: 0 ms | ||||
Inverter overload capability | 102% ~ 125%: transfer to bypass in 10 min; 125% ~ 150%: transfer to bypass in 1 min; > 150%: transfer to bypass in 0.5 s | ||||
Bypass overload capability | 102% ~ 125%: shut down in 20 min; 125% ~ 150%: shut down in 2 min; > 150%: shut down in 1 s | ||||
BATTERIES | |||||
DC voltage | Standard model: 240 Vdc; Long time model: 192 Vdc (168 V / 192 V / 216 V / 240 V optional) | ||||
Inbuilt battery of standard model | 20 × 7 Ah | / | 40 × 7 Ah | 40 × 9 Ah | 60 × 9 Ah |
Charging current | Long time model: 7 A supplied (additional 7 A is optional) Standard model: 1 A, 2 A, 3.5 A settable | ||||
Recharge time | Standard model: 90% capacity restored in 4 hours; Long time model: depend on the capacity of battery | ||||
SYSTEM | |||||
Efficiency | ≥ 93%, ECO mode 98% | ||||
Display | LCD+LED | ||||
Alarm | Battery mode, low battery, fans fault etc. | ||||
Max. parallel numbers | 6 | ||||
Communications | RS232 / USB (standard), RS485 / dry contacts / SNMP (optional) | ||||
EMI | IEC/EN62040-2 | ||||
EMS | IEC61000-4-2 (ESD) | ||||
IEC61000-4-3 (RS) | |||||
IEC61000-4-4 (EFT) | |||||
IEC61000-4-6/4-8/4-11 | |||||
OTHERS | |||||
Humidity | 20 ~ 90% RH @ 0-40℃ (non-condensing) | ||||
Noise level | ≤ 60 dB (1 m) | ≤ 60 dB (1 m) | |||
Standard Dimensions (W × D × H) (mm) | 350 × 655 × 732 (H) | ||||
350 × 785 × 858 (S) | 350 × 785 × 858 (S) | ||||
Standard Packaged dimensions (W × D × H) (mm) | 472 × 780 × 920 (H) | ||||
472 × 910 × 1050 (S) | 472 × 910 × 1260 (S) | ||||
Net weight (kg) | 55 (H), 110 (S) | 55 (H), 110 (S) | 60 (H), 155 (S) | 61 (H), 175 (S) | 65 (H), 235 (S) |
Gross weight (kg) | 65 (H), 125 (S) | 65 (H), 125 (S) | 70 (H), 170 (S) | 71 (H), 190 (S) | 75 (H), 250 (S) |
Derate capacity to 90% when the output voltage is adjusted to 360 Vac.
S means standard model, H means long time model.
All specifications subject to change without notice.