HOME > PRODUCTS > UPS 6 kVA ~ 10 kVA

UPS 6 kVA ~ 10 kVA

  • BRAND:Wenzhou Atele electric Co.,Ltd.
  • TEL:+86-577-62880175
  • Cellphone/Whatsapp: +86-13396988661
PRODUCT DETAILS

● High frequency on-line double conversion technology

● DSP (Digital signal processors) technology

● Active power factor correction (APFC), input power factor up to 0.99

● Output power factor 0.9

● Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70Hz)

● Auto sensing frequency

● 50 / 60 Hz frequency conversion

● Cold start

● Rear ventilation design and variable speed fan

● Effective software and hardware protection

● Flexible battery configuration (Settable 14 - 20 pcs batteries)

● Quick and stable charging, 90% capacity restored in 4 h (standard model UPS)

● Linear derating in low voltage input reducing battery discharging times

● Settable delayed start when power is restored

● Advanced battery management (ABM)

● Multiple functions settable via LCD: output voltage, battery quantity, EOD, EPO, ECO mode, frequency conversion mode and parallel enable

● Powerful background software for parameters configuration, function settings and online updating

● Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)


Available Options

● Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, maintenance bypass, EPO function, parallel function, battery temperature compensation and EMD environmental sensors

 

MODEL

EA906PS

EA906PH

EA9010PS

EA9010PH

Capacity

6 kVA / 5400 W

10 kVA / 9000 W

INPUT

Rated voltage

208 V / 220 V / 230 V / 240 Vac

Voltage range

110 ~ 160 Vac (linear derating between 50% and 100% load);

160 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)

Rated frequency

50 / 60 Hz (auto-sense)

Frequency range

40 ~ 70 Hz

Power factor

 ≥ 0.99

Total harmonic distortion (THDI)

≤ 5%

Bypass voltage range

-40% ~ +15% (settable)

OUTPUT

Voltage

208 V / 220 V / 230 V / 240 Vac (settable)

Voltage regulation

± 1%

Frequency

45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)

Waveform

Pure sine wave

Crest factor

3:1

Total harmonic distortion (THDV)

≤ 2% (linear load); ≤ 5% (non-linear load)

Transfer time

Mains mode to battery mode: 0 ms; Inverter mode to bypass mode: 0 ms

Inverter overload capability

102% ~ 125%: Transfer to bypass in 10 min;

125% ~ 150%: Transfer to bypass in 1 min;

> 150%: Transfer to bypass in 0.5 s

Bypass overload capability

102% ~ 125%: Shut down in 20 min;

125% ~ 150%: Shut down in 2 min;

> 150%: Shut down in 1 s

BATTERIES

DC voltage

192 VDC (168 / 192 / 216 / 240 Vdc optional)

Inbuilt battery

16 × 7 Ah

/

16 × 9 Ah

/

Charging current

Standard model: 1 A

Long time model: 1 A, 2 A, 3.5 A (settable)

Recharge time

Standard model (S): 90% capacity restored in 4 hours;

Long time model (H): depend on the capacity of battery

SYSTEM

Efficiency

≥ 93%, ECO mode 98%

Display

LCD+LED

Alarms

Battery mode, battery voltage low, fans fault etc.

Max. number of parallel connections

6

Communications

RS232 (standard), USB / RS485 / dry contacts / SNMP (optional)

EMI

IEC/EN62040-2

EMS

IEC 61000-4-2 (ESD)

IEC 61000-4-3 (RS)

IEC 61000-4-4 (EFT)

IEC 61000-4-5 (Surge)

OTHERS

Humidity

20 ~ 90% RH @ 0 ~ 40℃ (non-condensing)

Noise level

≤ 55 dB (1 m)

Dimensions (W × D × H) (mm)

191 × 462 × 710

191 × 462 × 350

191 × 462 × 710

191 × 462 × 350

Packaged dimensions (W × D × H) (mm)

308 × 640 × 896

267 × 573 × 436

308 × 640 × 896

267 × 573 × 436

Net weight (kg)

58.7

15.6

67.2

16.1

Gross weight (kg)

64.8

17.9

73.3

18.4

 ● Derate capacity to 70% in Frequency conversion mode and to 90% when the output voltage is adjusted to 208 Vac.

 ● S means standard model, H means long time model.

 ● All specifications subject to change without notice.

 ● Custom-made specifications are acceptable.