Number of poles: 1, 2 ,3, 4
Main Technical Parameters| Model Specification | |||||
| Grid operation voltage Un (V) | 200V 380V | 220V 380V | 220V 380V | 220V 380V | 220V 380V |
| Maximum continuous operating voltage Uc (V) | 385V 420V | 385V 420V | 385V 420V | 385V 420V | 385V 420V |
| Voltage protection level Up (kV) | ≤4.0 ≤4.5 | ≤3.4 ≤3.7 | ≤2.8 ≤3.2 | ≤2.4 | ≤1.8 ≤2.2 |
| Maximum discharge current | 150 | 120 | 100 | 80 | |
| Nominal discharge current | 100 | 80 | 60 | 40 | |
| Response time ns | <100 | ||||
| Access wire cross-sectional are a L/N (mm ²) | 20, 35 | 16, 25 | 16, 25 | 16, 25 | |
| Access ground wire cross-sectional Are a PE(mm ²) | 35 | 20, 35 | 25, 35 | 25, 35 | |
| Fuse or circuit breaker selection | 63A, 35A | 63A, 100A | 63A, 100A | 63A | |
| Cross-sectional area of the communication, alarm line | ≥1.5 | ||||
| Work environment | -40 ℃~ +85 ℃ | ||||
| Relative humidity | ≤95% | ||||
| Installation | Standard to the track | ||||
| Case material | Glass fiber reinforced plastic | ||||