HOME > PRODUCTS > Residual Current Breaker with Over-Current Protection

Residual Current Breaker with Over-Current Protection

  • BRAND:Wenzhou Atele electric Co.,Ltd.
  • TEL:+86-577-62880175
  • Cellphone/Whatsapp: +86-13396988661
PRODUCT DETAILS

The RGLE-32, RGLE1-40, and RGLE2-40 residual current breakers with over-current protection are mainly applied in the AC 50Hz or 60Hz circuits with the rated voltage and current not exceeding 240V and 40A respectively. They are mainly used to protect the illumination and power distribution systems in the buildings.

Our residual current device offers reliable protection against electric leakage, overload, short circuit, and other faults. The overvoltage protection function can also be provided upon request.

Dimensions and Mounting

Installation and Wiring Diagram
Please read carefully before installation, so as to install correctly.
Part name           Circuit diagram        Teardown method

① Pull down the DIN-RAIL fixing card
② Incline and put up the RCBO

Main Technical Parameters
Rated  Voltage (V)Rated  current (A)Rated  residual operating current In (MA)Rated  residual non-operating current In(MA)Breaking  times (s)Rated  short-circuit breaking capacity(A)Rated  residual breaking capacity (A)
In2In0.25A500A
2406,  10, 16, 20, 25, 32, 4030,  10015,  50010.050040.043000,  4500, 6000500

When the RCBO is used under normal conditions and the temperature is 30℃-50℃, the over-current motion characteristic is described in the following table.

Rated  current IN(A)Testing  current (A)Starting  conditionTesting  time (t)Testing  resultNote
6,10,16,20,  25,32,401.13inCold≥1hNon-motion
1.45inHot<1hMotionCurrent  will rise to rated value steadily within 5s
2.55inCold1~60sMotion
5inCold≥0.1sNon-motion
10inCold<0.1sMotion

For the residual current protection characteristic of the residual current circuit breaker with over-current protection, please see the table below.

Rated  residual operating current IN (MA)Rated  residual non-operating current INO (MA)Maximum  breaking time (s)
30,  10015,  500.1

Number of poles: 2P, 4P
Rated voltage: 240V/400V
Rated Current :6-63A
Residual operating current: 500mA, 300mA
Icu = Ics

Overall and Mounting Dimensions